Ensuring Commercial Electrical Safety & EPRA Compliance: Our EICR Audit at LeMac Building, Westlands

When managing high-stakes corporate infrastructure, electrical safety is not merely a operational detail—it is the backbone of risk management, business continuity, and regulatory compliance.

Recently, our engineering team at Expertech Electrical Contractors Ltd was commissioned to execute a comprehensive Electrical Installation Condition Inspection, Testing, and Compliance Audit for Geminia Insurance Company Limited at their offices in the iconic LeMac Building along Church Road, Westlands, Nairobi.

Here is an inside look at how our certified electrical engineers carried out the EICR assessment, rectified latent hazards, and validated full compliance with EPRA guidelines and Kenyan statutory standards.

The Challenge: Ensuring Zero-Downtime & Safety for Corporate Facilities

Commercial properties in fast-growing business hubs like Westlands, Nairobi require robust, failure-proof electrical systems. Over time, continuous load, thermal expansion, and minor physical wear can lead to:

  • Loose terminal terminations and contact points.
  • Overheating in circuit breakers and distribution boards.
  • Unnoticed electrical arcing, which poses severe fire risks.
  • Degradation of earthing and protective bonding mechanisms.

To secure their premise and fulfill corporate risk management protocols, Geminia Insurance needed a thorough Electrical Installation Condition Report (EICR) to verify system health and facilitate official regulatory certification.

Scope of Inspection & Technical Execution

Our lead technician, Dancan Omondi Omollo, alongside our field engineering team, executed a systematic, multi-stage inspection adhering strictly to BS 7671:2018 standards, the Energy Act 2019, and the Electric Power (Electrical Installation Work) Rules, 2006 (Legal Notice No. 115).

The project encompassed the following primary deliverables:

1. Thermal & Physical Inspection of Distribution Boards

We conducted visual and physical assessments of main switchgear and sub-distribution boards. During testing under load, our team identified loose miniature circuit breaker (MCB) terminal connections that were causing localized overheating due to insulation pinching.

  • Corrective Action: All affected MCB terminals were re-stripped, properly positioned, and torqued to manufacturer specifications using calibrated instruments to eliminate contact resistance and thermal buildup.

2. Lighting & Power Circuit Diagnostics

We tested ring final circuits, power outlets, and lighting infrastructure across the premises. Loose ceiling lighting connections were identified in the reception area, alongside an active arcing point caused by a faulty luminaire adapter.

  • Corrective Action: The loose ceiling connections were re-terminated securely, and the defective lighting point was safely isolated pending adapter replacement. Ring final circuits were confirmed to have satisfactory insulation integrity and proper mechanical cable support.

3. Earthing, Bonding & Power Quality Verification

Earthing is the single most critical safety layer in modern commercial buildings. Utilizing calibrated ground resistance testers, we verified the integrity of the main protective bonding and PME (Protective Multiple Earthing) connections:

  • Earth Electrode Resistance: Recorded at 4.45 Ω, well within the safe threshold criteria ().
  • Insulation Resistance: Measured at a high 120 MΩ across phases, phase-to-neutral, and neutral-to-earth.
  • Neutral-to-Earth Voltage: Verified at a clean 0.6 V AC.
  • Phase Balance & Voltage: Recorded a stable 3-phase supply of 417 V AC between phases and 237 V AC phase-to-neutral, with no current imbalance across phases under load.

Results & EPRA Regulatory Certification

Following our corrective maintenance on site, the installation was officially classified as SATISFACTORY FOR CONTINUED USE.

The completed technical report and field documentation—approved by Technical Director Eng. Oiro Washingtone and authorized signatories—formed the technical basis for issuing the official EPRA Electrical Completion Certificate in accordance with national power distribution guidelines.

Why Choose Expertech Electrical Contractors Ltd?

At Expertech, we provide end-to-end commercial electrical services, solar PV integration, power audits, and maintenance solutions tailored to protect your corporate investments.

  • Licensed Expertise: Certified Class B EPRA electricians and registered professional engineers.
  • Precision Testing: Calibrated instruments and comprehensive data-backed EICR documentation.
  • Safety First: Strict adherence to Kenyan energy laws, OSHA standards, and international electrical codes.

Need an Electrical Safety Audit or EPRA Compliance Certificate for Your Facility?

Protect your workplace, reduce fire risks, and maintain full statutory compliance with Kenya's premier electrical engineering firm.

  • 📞 Direct Call / WhatsApp: +254 105 159 533 | +254 740 728 529
  • ✉️ Email Us: info@expertech.co.ke
  • 🌐 Visit Our Portal: www.expertech.co.ke